Manitowoc I0500 Spezifikationen Seite 184

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 270
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 183
184 Part Number STH025 02/12
Symptom #2 Machine is running and the display
indicates “HPC Fault” and an alert triangle
1. Navigate to the event log on the Service menu.
Scroll down to HPC Fault #5. Open the event and
view when and how often HPCO Fault has
occurred.
2. If this is a one time event it may be intermittent
and caused by conditions around the unit
changing. For example: High ambient
temperature, water turned off to condenser (water
cooled unit) etc.
3. Run the system to see if the control trips at the
rated pressure. If HPCO opens at a pressure
significantly lower than the control setting of 440
psig replace the HPCO.
4. If the control opens at the correct pressure (+-10
lbs) find the root cause - Fan motor, dirty condenser,
refrigeration system issue, etc.
Seitenansicht 183
1 2 ... 179 180 181 182 183 184 185 186 187 188 189 ... 269 270

Kommentare zu diesen Handbüchern

Keine Kommentare