Manitowoc CVD1375 Spezifikationen Seite 165

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 204
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 164
–163–
FREEZE CYCLE HEADMASTER CONTROL VALVE
FAILURE LIST
CVD0875/CVD1075/CVD1475/CVD1875/CVD2075
Valve not maintaining pressures
Non-approved valve. Install a Manitowoc head
pressure control valve with proper setting.
Discharge pressure extremely high; liquid line
entering receiver feels hot
Valve stuck in bypass. Replace valve.
Fan cycling control cycles condenser fan motor;
liquid line entering receiver fluctuates between
warm and cold
Valve not bypassing. Replace valve.
Discharge pressure low; liquid line entering
receiver feels warm to hot
Ice machine low on charge. Refer to “Low on
Charge Verification.”
Fan cycling control cycles condenser fan motor;
liquid line entering receiver feels warm to hot
Ice machine low on charge. Refer to “Low on
Charge Verification.”
CVD0675
Valve not maintaining pressures
Non-approved valve. Install a Manitowoc head
pressure control valve with proper setting.
Discharge pressure extremely high; liquid line
entering receiver feels hot
Valve stuck in bypass. Replace valve.
Discharge pressure low; liquid line entering
receiver feels cold
Valve not bypassing. Replace valve.
Discharge pressure low; liquid line entering
receiver feels warm to hot
Ice machine low on charge. Refer to “Low on
Charge Verification.”
Seitenansicht 164
1 2 ... 160 161 162 163 164 165 166 167 168 169 170 ... 203 204

Kommentare zu diesen Handbüchern

Keine Kommentare